8.2 Programming Mode Constants
8-5
8.2 Programming Mode Constants
8.2.1 Application Constants: b
J
Operation Mode Selections: b1
Name
Change
Control Methods
Constant
Number
Display
Description
Setting
Range
Factory
Setting
during
Opera-
tion
V/f
V/f
with
PG
Open
Loop
Vector
Flux
Vector
Page
Reference selection
Used to set the input method for
the frequency reference.
0: Digital Operator
1: Control circuit terminals (ana-
log inputs).
6-4
b1-01
Reference Source
2: MEMOBUS transmission (us-
ing SI-K2)
3: Option Card
4: MEMOBUS transmission (for
CP-717)
0to4 1
×
Q Q Q Q
6-7
b1-02
Operation method
selection
Used to set the source of the run
command.
0: Digital Operator
1: Control circuit terminals (se-
quence inputs).
0to4 1
×
Q Q Q Q
6-9
Run Source
2: MEMOBUS transmission (us-
ing SI-K2)
3: Option Card
4: MEMOBUS transmission (for
CP-717)
b1-03
Stopping method
selection
Used to set the stopping method
used when a stop command is in-
put.
0: Ramp to stop
1: Coast to stop.
2: DC injection braking stop:
(Stops faster than coast to
0to3 0
×
Q Q Q Q
6-12
Stopping Method
stop, no regenerative opera-
tion.)
3: Coast to stop with timer: Run
commands are disregarded
during deceleration.
:Only settings 0 and 1 can be
used with flux vector control.
b1-04
Prohibition of reverse
operation
0: Reverse enabled
0, 1 0
×
B B B B
6-11
Reverse Oper
1: Reverse disabled
,
b1-05
Operation selection
for setting of E1-09 or
less
Used to set the method of opera-
tion when the frequency reference
input is less than the minimum
output frequency (E1-09).
0: Run at frequency reference
(E1-09 not effective).
1: STOP (Frequencies below
E1-09 in the coast to stop
0to3 0
× × × ×
A
6-31
Zero-Speed Oper
s
a
e.
2: Run at min. frequency.
(E1-09)
3: Run at zero speed (Frequen-
cies below E1-09 are zero)
:This function is only available
in with flux vector control.
8