User Constants
8.2.5 Options Constants: F
8-24
8.2.5 Options Constants: F
J
PG Option Setup: F1
Con-
Name
S
Change
Control Methods
Con
stant
Num-
ber
Display
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
V/f
V/f
with
PG
Open
Loop
Vector
Flux
Vector
Page
F1 01
PG constant
Sets the number of PG (pulse generator or
encoder) pulses.
0to
600
×
×
Q
×
Q
6-28
F1-01
PG Pulse/Rev
encoder)
pulses.
:Sets the number of pulses per motor rev-
olution.
0
to
60000
600
× ×
Q
×
Q
6
28
6-42
F1-02
Operation
selection at PG
open circuit
Sets the PG disconnection stopping method.
0: Ramp to stop (Deceleration stop using
deceleration time 1, C1-02.)
1: Coast to stop
2: Fast sto
p
(
Emer
g
enc
y
sto
p
usin
g
the
0to3 1
× ×
B
×
B
6-29
6
42
F1 02
PG Fdbk Loss
Sel
2:
Fast
stop
(Emer
gency
stop
using
the
fast-stop time, C1-09.)
3: Continue operation (To protect the mo-
tor or machinery, do not normally make
this setting.)
0
to
3
1
×
×
B
×
B
6-42
F1-03
Operation
selection at
overspeed
Sets the stopping method when an over-
speed (os) fault occurs.
0: Ramp to stop (Deceleration stop using
deceleration time 1, C1-02.)
1: Coast to stop
2
Ft
t
(E
t
i
th
0to3 1
× ×
B
×
B
6-30
6
43
F1 03
PG Overspeed
Sel
2: Fast stop (Emergency stop using the
fast-stop time, C1-09.)
3: Continue operation (To protect the mo-
tor or machinery, do not normally make
this setting.)
0
to
3
1
×
×
B
×
B
6-43
F1-04
Operation
selection at
deviation
Sets the stopping method when a speed
deviation (DEV) fault occurs.
0: Ramp to stop (Deceleration stop using
deceleration time 1, C1-02.)*1
1: Coast to stop*1
2: Fast stop (Emergency stop using the
fast-stop time, C1-09.)*1
3: Continue operation (DEV is displayed
and operation continued.)*1
4: Decleration to stop using deceleration
time1(c102)*2
5: Coast to stop*2
6:
Emer
gency
atop
using
the
emer
gency
0to7 3
× ×
B
×
B
6-30
6
43
F1 04
PG Deviation
Sel
6
:
E
mergency a
t
op us
i
ng
th
e emergency
stop time (C109)*2
7: Continue Operation (Displays ”DEV”
and continues cntrol)*2
*1 Speed agreement conditions: The fre-
quency reference and output frequency
were entered in the speed agree detec-
tion width set in L402.
*2 Speed agreement conditions: The fre-
quency reference and the (actual) motor
speed based on the PG feedback value
were entered in the speed agree detec-
tion width set in L402.
0
to
7
3
×
×
B
×
B
6-43
PG rotation
0: Phase A leads with forward run com-
mand. (Phase B leads with reverse run
command )
F1-05
PG Rotation
Sel
command.
)
1: Phase B leads with forward run com-
mand. (Phase A leads with reverse run
command.)
0, 1 0
× ×
B
×
B
6-28
F1-06
PG division
rate (PG pulse
monitor)
Sets the division ratio for the PG speed con-
trol card pulse output.
Division ratio = (1+ n) /m (n=0,1 m=1 to
32
)
F106 =
j jj
1 to 132 1
× ×
B
×
B
6-29
F1 06
PG Output Ra-
tio
:This constant is only effective when a
PG-B2 is used.
The possible division ratio settings are:
1/32 F1-06 1.
mn
1
to
132
1
×
×
B
×
B
6
29
8