Trial Operation
5.2.5 Autotuning
5-4
5.2 Trial Operation Procedures
5.2.1 Power ON
J Checkpoints before Turning ON the Power Supply
D Check that the power supply is of the correct voltage.
200 V class: 3-phase 200 to 230 VDC, 50/60 Hz
400 V class: 3-phase 380 to 460 VDC, 50/60 Hz
D
Make sure that the motor output terminals (U, V, W) and the motor are connected correctly.
D
Make sure that the Inverter control circuit terminal and the control device are wired correctly.
D
Set all Inverter control circuit terminals to OFF.
D
When using a PG Speed Control Card, make sure that it is wired correctly.
D
Make sure that the motor is not connected to the mechanical system (no-load status)
5.2.2 Checking the Display Status
If the Digital Operators display at the time the power is connected is normal, it will read as follows:
Frequency Ref
U101 = 0.00 HZ
[Normal]
The frequency reference monitor is
displayed in the data display section.
When an fault has occurred, the details of the fault will be displayed instead of the above display. In that
case, refer to Section 9 Maintenance Operations. The following display is an example of a fault display.
UV
Under Voltage
[Fault]
The display will differ depending
on the type of fault.
5.2.3 Initializing Constants
D
When replacing the controller PCB, check the Inverter capacity (kVA) in o2-04 first and then initialize
constants to the factory settings. There is no need to initialize constants the first time trial operation
is performed after purchasing the Inverter.
D
To initialize the constants, set “2220” in A1-03 (Initialize).
D
After initialization, the access level is set to Quick-start (A1-01). The following table shows the setting
method for Quick-start.
Use the following procedure to initialize constants.
Step Key Sequence Digital Operator Display Remarks
Frequency Ref
U101 = 0.00 HZ
1
MENU
G5: Main Menu :
Operation
Displays operation mode.
2
G5: Main Menu :
Initialize
Displays initialize mode.
3
DATA
ENTER
Select Language
English
Puts the Inverter in initialize mode.
4
Press 3 times.
Initialize
Select
Displays the Initialize display.
5
DATA
ENTER
A1-03 = 0:::
Select
Displays the constant setting for
A1-03.
6
A1-03 = 222012345
2wire Initial
Initializes for a 2-wire sequence.
7
DATA
ENTER
Entry Accepted
Writes the set values. “Entry Ac-
cepted” is displayed for approximate-
ly 0.5 seconds.
Initialize
Select
Returns to the Initialize display.
8
ESC
G5: Main Menu :
Initialize
Returns to the initialize mode display.