User Constants
8.2.8 Operator Constants: o
8-44
J Multi-function Selections: o2
Name
Change
Control Methods
Constant
Number
Display
Description
Setting
Range
Factory
Setting
during
Opera-
tion
V/f
V/f
with
PG
Open
Loop
Vector
Flux
Vector
Page
o2-01
LOCAL/REMOTE key
enable/disable
Sets the Digital Operator Local/
Remote Key
0: Disabled
0, 1 1
×
B B B B
7-98
Local/remote key
1: Enabled (Switches between
the Digital Operator and the
constant settings.)
,
o2-02
STOP key during
control circuit terminal
operation
Sets the Stop Key in the run
mode.
0: Disabled (When the run com-
mand is issued from and exter-
nal terminal, the Stop Key is
0, 1 1
×
B B B B
7-99
Oper STOP Key
,
disabled.)
1: Enabled (Effective even dur-
ing run.)
o2-03
User constant initial
value
Clears or stores user initial values.
0: Stores/not set
1: Begins storing (Records the
set constants as user initial val-
ues.)
0to2 0
×
B B B B
7-99
User Defaults
:
c
ear
ears a
recor
e
user initial values)
:When the set constants are re-
corded as user initial values,
1110 will be displayed in the
Initialize mode (A1-03.)
kVA selection
0toFF
*
o
-
Inverter Model #
Do not set.
*
×
7-
o2-05
Frequency reference
setting method selec-
tion
When the frequency reference is
set on the Digital Operator fre-
quency reference monitor, sets
whether the Enter Key is neces-
sary.
0: Enter Key needed
0, 1 0
×
A A A A
7-99
Operator M.O.P.
1: Enter Key not needed
:When set to 1, the Inverter ac-
cepts the frequency reference
without Enter Key operation.
o2-06
Operation selection
when digital operator
is disconnected
Sets the operation when the Digi-
tal Operator is disconnected.
0: Disabled (Operation continues
even if the Digital Operator is
disconnected.)
0, 1 0
×
A A A A
7 - 100
Oper Detection
1: Enabled (OPR is detected at
Digital Operator disconnec-
tion. Inverter output is cut off,
and fault contact is operated.)
o2-07
Cumulative operation
time setting
Sets the cumulative operation time
in hour units.
0to
0
×
A A A A
7 - 100
Elapsed Time Set
:Operation time is calculated
from the set values.
6
3
o2-08
Cumulative operation
time selection
0: Cumulative time when the In-
verter power is on. (All time
while the Inverter power is on
is accumulated.)
0, 1 0
×
A A A A
7 - 100
Elapsed Time Run
1: Cumulative Inverter run time.
(Only Inverter output time is
accumulated.)
,
o2-09
Initialize mode selec-
tion
Do not set. 0to2 0
×
A A A A
−
Init Mode Sel
.
* The factory setting depends upon the Inverter capacity. The values for a 200 V class Inverter of 0.4 kW will be displayed.
8