User Constants
8.2.4 Motor Constant Constants: E
8-22
* 3. The setting range is 0.00 A to the motor’s rated current − 0.1 A.
J
Motor 2 Control Method: E3
Name
Change
Control Methods
Constant
Number
Display
Description
Setting
Range
Factory
Setting
during
Opera-
tion
V/f
V/f
with
PG
Open
Loop
Vector
Flux
Vector
Page
E3-01
Motor 2 control meth-
od selection
0: V/f control
1: Open loop vector
0to3 2
×
A A A A
−−
Control Method
2: Open-loop vector control
3: Flux vector control
J
Motor 2 V/f Pattern: E4
Con-
Name
Change
Control Methods
stant
Num-
ber
Display
Description
Setting
Range
Factory
Setting
during
Opera-
tion
V/f
V/f
with
PG
Open
Loop
Vector
Flux
Vector
Page
E4-01
Motor 2 max.
output frequen-
cy
40.0 to
400.0
60.0
×
A A A A
6-26
V/F2 Max Freq
.
Motor 2 max.
voltage
0.0 to
200
E4-02
V/F2 Max Volt-
age
Output voltage (V)
VMAX
.
*1
*1
×
A A A A
6-26
E4-03
Motor 2 max.
voltage fre-
quency
(E4-02)
0.0 to
60.0
×
A A A A
6-26
V/F2 Base
Freq
VC
(E4-05)
400.0
.
E4-04
Motor 2 mid.
output frequen-
cy 1
VMIN
(E4-07)
Fre-
quency
(Hz)
0.0 to
400.0
3.0
*2
×
A A A
×
6-26
V/F2 Mid Freq
FMIN
(E4-06)
FB
(E4-04)
FA
(E4-03)
FMAX
(E4-01)
.
E4-05
Motor 2 mid.
output frequen-
cy voltage 1
:To set V/f characteristics in a straight
line, set the same values for E4-04
0.0 to
255.0
11.0
*
×
A A A
×
6-26
V/F2 Mid Volt-
age
and E4-06. In this case, the setting for
E4-05 will be disregarded.z
Alwa
s ensure that the four fre
uen-
*1
*1
E4-06
Motor 2 min.
output frequen-
cy
cies are set in the following manner:
E4-01 (FMAX) ≥ E4-03 (FA) >
E4-04 (FB) ≥ E4-06 (FMIN)
0.0 to
400.0
0.5
*2
×
A A A A
6-26
V/F2 Min Freq
.
E4-07
Motor 2 min.
output frequen-
cy voltage
0.0 to
255.0
2.0
*
×
A A A
×
6-26
V/F2 Min Volt-
age
*1
*1
* 1. These are values for a 200 V class Inverter. Values for the 400 V class Inverter are double.
* 2. When the control method is changed, the Inverter reverts to factory settings. (The open-loop vector control factory settings
will be displayed.)
8