YASKAWA CIMR-G5A Series - PG Pulse Output Monitor Division Rate: F1-06; PG Rotation Direction Setting; PG Disconnection Stopping Method: F1-02, F1-14

YASKAWA CIMR-G5A Series
355 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
6.4 Flux Vector Control
6-29
VS-616G5 Motor PG (encoder)
Forward
Pulse output
Phase A
Phase B
Phase A
Phase B
[Setting: 0] [Setting: 1]
D
Forward rotation in a typical motor (applicable Yaskawa PG: made by Thermtac):
Forward
The motor output shaft rotates in
the counterclockwise direction
with a forward inverter reference.
Phase A
Phase B
Forward rotation
D
Phase A leading in a typical PG:
Phase A leads when the input axis rotates clockwise.
Phase A
Phase B
Fig 6.12 PG Rotation Direction Setting
J
PG Pulse Output Monitor Division Rate: F1-06
D
This constant is effective only when a PG-B2 PG Control Card is used.
D
It sets the division ratio used when the pulse monitor output is connected to a pulse input device.
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
g
during
Opera-
tion
Setting
Range
Unit
Factory
Setting
V/f
Control
V/f with
PG
Open
Loop
Vector
Flux
Vector
F1-06
PG division rate (PG
pulse monitor)
×
1 to 132 1
×
B
×
B
D
The first digit in the setting (0 or 1) is n and the second two digits (01 to 32) are m. The division ratio
is calculated from n and m with the following equation:
Division ratio = ( 1 + n )/m Setting Ranges n: 0, 1 m: 1 to 32
F1-06 = j
jj
mn
D
Possible division rate settings are as follows: 1/32 F1-06 1. For example, if the division rate is
1/2 (a setting of “2”), the monitor output will be half of the number of pulses output from the PG.
J
Fault Detection Functions: F1-02 to F1-04, F1-08 to F1-11, F1-14
PG Disconnection Stopping Method: F1-02, F1-14
D
Sets the PG open-circuit detection time and stopping method that is used when a break is detected in
the PG cable (PGO).
User
Change
during
Setting
Factory
Valid Access Levels
User
Constant
Number
Name
g
during
Opera-
tion
Setting
Range
Unit
Factory
Setting
V/f
Control
V/f with
PG
Open
Loop
Vector
Flux
Vector
F1-02
Operation selection
at PG open circuit
×
0to3 1
×
B
×
B
F1-14
PG open-circuit
detection time
×
0.0 to 10.0 s 2.0
×
A
×
A
6