8.2 Programming Mode Constants
8-39
J Reference Detection: L4
C
Name
S
Change
Control Methods
Constant
Number
Display
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
V/f
V/f
with
PG
Open
Loop
Vector
Flux
Vector
Page
L4-01
Speed agree detec-
tion level
Effective when “Desired frequen-
cy (ref/setting) agree 1,” “Fre-
quency detection 1,” “Frequency
detection 2,” are set for multi-
fi
0.0 to
400 0
0.0
×
B B B B
7-90
L4 01
Spd Agree Level
detect o
,
ae
set
o
ut
function output.
Frequencies to be detected are set
in Hz units.
400.0
0
.
0
×
B
B
B
B
7
90
L4-02
Speed agree detec-
tion width
Effective when “Frequency (ref/
out) agree 1,” “Desired frequency
(ref/setting) agree 1,” “Frequency
detection 1,” “Frequency detec-
tion
2
are
set
for
multi-function
0.0 to
20 0
2.0
×
B B B B
7-90
L4 02
Spd Agree Width
t
i
on
2”
are set
f
or mu
l
t
i
-
f
unct
i
on
output.
Sets the frequency detection width
in Hz units.
20.0
2
.
0
×
B
B
B
B
7
90
L4-03
Speed Agree detec-
tion level (+/)
Effective when “Desired frequen-
cy (ref/setting) agree 2,” “Fre-
quency detection 3,” “Frequency
detection 4,” are set for multi-
fi
400.0
to
0.0
×
A A A A
7-90
L4 03
Spd Agree Lvl +
detect o
,
ae
set
o
ut
function output.
Frequency detection width is set
in Hz units.
to
+ 400.0
0
.
0
×
A
A
A
A
7
90
L4-04
Speed agree detec-
tion width (+/)
Effective when “Frequency (ref/
out) agree 2,” “Desired frequency
(ref/setting) agree 1,” “Frequency
detection 3,” “Frequency detec-
tion
4
are
set
for
multi-function
0.0 to
20 0
2.0
×
A A A A
7-90
L4 04
Spd Agree Wdth +
t
i
on
4”
are set
f
or mu
l
t
i
-
f
unct
i
on
output.
Frequency detection width is set
in Hz units.
20.0
2
.
0
×
A
A
A
A
7
90
L4-05
Operation when fre-
quency reference is
missing
0: Stop (Operation follows the
frequency reference.)
1: Operation at 80% speed con-
tinues. (At 80% of speed be-
fore the frequency reference
was
lost)
0, 1 0
×
A A A A
7-91
Ref Loss Sel
was lost)
:Frequency reference is lost:
Frequency reference dropped
over 90% in 400 ms.
J Fault Restart: L5
C
Name
S
Change
Control Methods
Constant
Number
Display
Description
Setting
Range
Factory
Setting
Change
during
Opera-
tion
V/f
V/f
with
PG
Open
Loop
Vector
Flux
Vector
Page
L5-01
Number of auto re-
start attempts
Sets the number of auto restart at-
tempts.
Automaticall
y
restarts after a fault
0to10 0
×
B B B B
7-93
L5 01
Num of Restarts
Automatically
restarts
after
a
fault
and conducts a speed search from
the run frequency.
0
to
10
0
×
B
B
B
B
7
93
L5-02
Auto restart operation
selection
Sets whether a fault contact output
is activated during fault restart.
0: Not output (Fault contact is
not
activated )
0, 1 0
×
B B B B
7-94
L5 02
Restart Sel
not activated.)
1: Output (Fault contact is acti-
vated.)
0
,
1
0
×
B
B
B
B
7
94
8

Table of Contents

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the YASKAWA CIMR-G5A Series and is the answer not in the manual?

YASKAWA CIMR-G5A Series Specifications

General IconGeneral
BrandYASKAWA
ModelCIMR-G5A Series
CategoryInverter
LanguageEnglish

Related product manuals