7.5.6 Protective Functions: L
7-90
Stall Prevention Level During Running: L3-06
User
Change
Valid Access Levels
Constant
Number
Name
during
Opera-
tion
Setting
Range
Unit
Factory
Setting
V/f
Control
V/f with
PG
Open
Loop
Vector
Flux
Vector
L3-06
Stall prevention lev-
el during running
×
30 to 200 % 160
B B
× ×
D
This setting is valid when L3-05 is set to 1 or 2.
D
Normally it isn’t necessary to change this setting.
D
Decrease this setting when the motor capacity is small compared to the Inverter capacity or stalling
occurs when the motor is operated with the factory setting.(Set this current value as a percentage of
the Inverter’s rated current, i.e., 100% corresponds to the Inverter’s rated current.)
Output current
Time
Output frequency
Time
The output frequency is controlled to prevent
stalling.
Deceleration rate: C1-02 or C1-04
L3-06 (Run stall prevention level)
Fig
7.50
Run Stall Prevention Function: L3-05 = 1 or 2
J
Frequency Detection Settings: L4-01 to L4-05
User
Change
Valid Access Levels
Constant
Number
Name
during
Opera-
tion
Setting
Range
Unit
Factory
Setting
V/f
Control
V/f with
PG
Open
Loop
Vector
Flux
Vector
L4-01
Speed agree detec-
tion level
×
0.0 to 400.0 Hz 0.0
B B B B
L4-02
Speed agree detec-
tion width
×
0.0 to 20.0 Hz 2.0
B B B B
L4-03
Speed agree detec-
tion level (+/−)
×
−400.0 to
+400.0
Hz 0.0
A A A A
L4-04
Speed agree detec-
tion width (+/−)
×
0.0 to 20.0 Hz 2.0
A A A A
D
Set these constants when outputting one of the frequency agree or frequency detection signals from
a multi-function output. Table 7.13 shows the relationship between these constants and the output sig-
nals.
Table 7.13 Constants and Output Signals
Constant Related output settings Constant function
Speed Agree Level
(Absolute value)
Fref/Set Agree 1
Frequency Detection 1
Frequency Detection 2
Set the speed that you want to detect in
Hz.
The set speed is an absolute value, so the
speed is detected in forward or reverse.
Speed Agree Width
(Absolute value)
Fref/Fout Agree 1
Fref/Set Agree 1
Frequency Detection 1
Frequency Detection 2
Set the speed detection range in Hz.
7