8.2 Programming Mode Constants
8-33
J Analog Outputs: H4
Name
Change
Control Methods
Constant
Number
Display
Description
Setting
Range
Factory
Setting
during
Opera-
tion
V/f
V/f
with
PG
Open
Loop
Vector
Flux
Vector
Page
H4-01
Monitor selection (ter-
minal 21)
Sets the number of the monitor
item to be output (U1-
jj
) from
terminal 21.
1to38 2
×
B B B B
7-82
Terminal 21 Sel
:4, 10, 11, 12, 13, 14, 25, 28, 34,
35 cannot be set and 29 to 31
are not used.
Gain (terminal 21)
Sets the multi-function analog
output 1 voltage level gain.
0.00 to
H4-02
Terminal 21 Gain
Sets whether the monitor item
output will be output in multiples
of 10 V.
.
2.50
1.00
f
B B B B
7-82
Bias (terminal 21)
Sets the multi-function analog
output 1 voltage level bias.
−10.0 to
H4-03
Terminal 21 Bias
Sets output characteristic up/down
parallel movement as a percentage
of 10 V.
.
+10.0
0.0
f
B B B B
7-82
H4-04
Monitor selection (ter-
minal 23)
Sets the number of the monitor
item to be output (U1-
jj) from
terminal 23.
1to38 3
×
B B B B
7-82
Terminal 23 Sel
:4, 10, 11, 12, 13, 14, 25, 28, 34,
35 cannot be set and 29 to 31
are not used.
Gain (terminal 23)
Sets the multi-function analog
output 2 voltage level gain.
0.00 to
H4-05
Terminal 23 Gain
Sets whether the monitor item
output will be output in multiples
of 10 V.
.
2.50
0.50 f
B B B B
7-82
Bias (terminal 23)
Sets the multi-function analog
output 2 voltage level bias.
−10.0 to
H4-06
Terminal 23 Bias
Sets output characteristic up/down
parallel movement as a percentage
of 10 V.
.
+10.0
0.0
f
B B B B
7-82
H4-07
Analog output signal
level selection
Sets the signal output level for
multi-function outputs 1 and 2
(terminals 21, 23.)
0: 0 to +10 V output
0, 1 0
×
B B B B
7-82
AO Level Select
1: 0 to +10 V output
:The optional Analog Monitor
Card may also be used with this
setting.
,
J MEMOBUS Communications: H5
Name
Change
Control Methods
Constant
Number
Display
Description
Setting
Range
Factory
Setting
during
Opera-
tion
V/f
V/f
with
PG
Open
Loop
Vector
Flux
Vector
Page
Station address
’
H5-01
Serial Comm Adr
Set the Inverter’s node address. 0to20 1F
×
A A A A
−−
Communication
Set the baud rate for 6CN ME-
MOBUS communications.
0: 1200 bps
H5-02
speed selection
1: 2400 bps
2: 4800 bps
3: 9600 bps
0to4 3
×
A A A A
−−
Serial Com Sel
4: 19200 bps
8