8.2 Programming Mode Constants
8-43
8.2.8 Operator Constants: o
J Monitor Select: o1
Con-
Name
Change
Control Methods
stant
Num-
ber
Display
Description
Setting
Range
Factory
Setting
during
Opera-
tion
V/f
V/f
with
PG
Open
Loop
Vector
Flux
Vector
Page
o1-01
Monitor selec-
tion
Set the number of the monitor item to be
displayed in the earliest 4 monitor items.
(U1-
jj
)
4to38 6
f
B B B B
7-97
Monitor Select
:The output monitor voltage (factory set-
ting) can be changed.
o1-02
Monitor selec-
tion after pow-
er up
Sets the monitor item to be displayed when
the power is turned on.
1: Frequency reference
1to4 1 f
B B B B
7-97
Power-On
Monitor
2: Output frequency
3: Output current
4: The monitor item set for o1-01
o1-03
Frequency
units of refer-
ence setting
and monitor
Sets the units that will be set and dis-
played for the frequency reference and
frequency monitor.
0: 0.01 Hz units
1: 0.01% units (Maximum output fre-
quency is 100%)
2 to 39: r/min units (Sets the motor poles.)
40 to 39999: User desired display
Set the desired values for
setting and display for the
0to
39999
0
×
B B B B
6-7
Display Scaling
max. ou
pu
requency.
j jjjj
Example: When the max. output frequen-
cy value is 200.0, set 12000
Set four digits without the
decimal point
Set the position of the dec-
imal point in the first digit.
o1-04
Frequency
units of
constant set-
ting
Set the V/f pattern setting units. (E1-04, 06,
09 set units)
0: Hz units
1: r/min units
0, 1 0
× × × ×
B
7-32
Display Units
:Effective only in the flux vector control
mode.
o1-05
Constant No.
display selec-
tion
Set the Operator constant number display
method.
0: Normal dis
la
e.
., A1-00
0, 1 0
×
A A A A
7-98
Address Dis-
play
.
.,
1: Display MEMOBUS communications
register address
,
8