3 608 878 300 Tightening Technology | Bosch Rexroth AG 179/641
System 350 | 3 608 878 300/2019-03
5.6.2 Normal tightening process with program change and without results reset
(1) Input, (2) Output
There is a delay between OK/NOK and CyCmp during results output, e.g. via the serial interface module.
The OK/NOK signal is applied directly after the end of the tightening sequence and CyCmp only after the
result has been processed. After results processing, the result is output. Results output is thus not always
completed after a sequence end for single-channel tightenings (see CyCmp on page 143). This delay
depends on the data output and can last from several 100 ms up to several seconds.
5.6.3 Cancelation of a tightening process by removing the start signal
(1) Input, (2) Output