3 608 878 300 Tightening Technology | Bosch Rexroth AG 509/641
System 350 | 3 608 878 300/2019-03
6.13.4 Diagnosis and troubleshooting
For diagnosis, the following two options are available:
Detailed text protocol
This protocol can be accessed via BS350 under System test Diagnosis QDA.
Sequence trace
The sequence trace can be accessed via BS350 under System test ... FF3 or FF4.
BS350 error list for system errors
6.13.4.1 Free memory
Intermediate storage of data is realized on the inserted CF350 (memory card). The data is created in
directory /ata1a/qda. There, different sub-directories with files are created and deleted after successful
transmission to the target server.
The intermediate memory is checked as follows:
On start of the QDA protocol:
If no CF350 (memory card) is inserted or if it cannot be read, the data service is not started and a
class 3 system error (2028: "Results output: CF card access error") is logged.
If more than 98% of the capacity on the memory card is occupied, the data service is not started and
a class 3 system error (2028: "Results output: CF card access error") is logged.
After each tightening process, prior to saving of a new data set in the intermediate memory:
If no CF350 (memory card) is inserted or if it cannot be read, the data service is not started and a
class 3 system error (2028: "Results output: CF card access error") is logged.
If a CF350 (memory card) is inserted, the occupied capacity is checked:
–> 80%
An acknowledgeable system error (2023: "Results output: CF card warning level") class 3 is
triggered.
–< 90%
Ok, a potentially active system error (2024: "Results output: CF card full") reset.
–> 90%
A non-acknowledgeable system error (2024: "Results output: CF card full") class 4 is triggered.
The error is not reset (acknowledged) before the remaining capacity is < 90%.
6.13.4.2 Error during transmission
Errors during transmission to the QDA server are logged in the sequence protocol. No I/O signal is set.