6.8.3 Example: Calculation of the data volume for results files
Prerequisite
• 4-step tightening program respectively with torque/angle target function and torque/angle/gradient
monitoring function
• 2000 graph points
Assumptions
• The application part can be ignored for theoretical calculation of the total size of the file.
• Always user-friendly formatting ( -> file size is approx. 20 % higher)
• Single channel without anything: 10 kBytes
• Single-channel graph data torque/angle/time, base64 coding: 40 kBytes
• Single-channel graph data torque/angle/time, without base64 coding: 70 kBytes
• Single-channel graph data, all with base64 coding: 75 kBytes
• Single-channel graph data, all without base64 coding: 120 kBytes
Calculation:
Application = Single channel x Number of channels
Table 6–134: Calculation of the data volume
Activation
Graph data base64 coding User-friendly
formatting
Size in kBytes
Single channel No - Yes 8
Torque/angle/time Yes Yes 40
1)
Torque/angle/time No Yes 68
All Yes Yes 72
All No Yes 122
2)
Application
1 channel
No - Yes 9
Torque/angle/time Yes Yes 41
Torque/angle/time No Yes 69
All Yes Yes 73
All No Yes 122
Application
20 channel
No - Yes 155
Torque/angle/time Yes Yes 797
1)
Torque/angle/time No Yes 1364
All Yes Yes 1473
All No Yes 2197
2)
Torque/angle/time Yes No 734
Torque/angle/time No No 1179
All Yes No 1371
All No No 1912
Example
1)
20 channels x 40 kBytes (single-channel graph data torque/angle/time, base64 coding):
Example
2)
20 channels x 125 kBytes (Single-channel graph data, all without base64 coding)