Detailed Descriptions of the Fieldbus Network Adapters 112
4.4.28 0x113C 0x113F Save Module Parameters
Load default module parameters (0x113C 0x113D) loads the default parameter set of all
modules (LOAD). This conforms to the Standard option in the web server.
Save module parameters (0x113E 0x113F) stores the current image of all module
parameters in the network adapter (SAVE). Subsequent changes will not be considered
unless they are saved again. There is no need to enter parameters again after restarting the
network adapter. This conforms to the Yes option in the web server.
Inputs in both register in the Motorola format follow this scheme:
“LOAD“
“SAVE“
Letter of the alphabet
L
O
A
D
S
A
V
E
ASCII code decimal
076
079
065
068
083
065
086
069
ASCII hexadecimal
4C
4F
41
44
53
41
56
45
Input in register no.
0x113C
0x113D
0x113E
0x113F
Hexadecimal
4C4F
4144
5341
5645
Decimal
19535
16708
21313
22085
Using the Intel format, the inputs follow “DAOL“ and “EVAS“: