User Manual Section 5
GFK-2958L May 2021
Detailed Description of I/O Modules 334
5.29.5 Diagnostic Data EP-3468
Name
Bytes
Bit
Description
Default
Error indicator
0
0
Module error
1
Internal error
2
External error
3
Channel error
0
4
Error
5
Reserved
0
6
Reserved
0
7
Parameter error
Module type
1
0
Module Type
0x05
1
2
3
4
Channel information available
1
5
Reserved
0
6
Reserved
0
7
Reserved
0
Error byte 2
2
0-7
Reserved
0
Error byte 3
3
0-2
Reserved
0
3
Internal diagnostic FIFO full
4
Power supply fault
5
Reserved
0
6
Reserved
0
7
Reserved
0
Channel type
4
0-6
Channel type
0x74
7
Reserved
0
Diagnostic bits
per channel
5
Number of diagnostic bit per
channel
8
Number of
channels
6
Number of similar channels
per module
8
Channel error
7
0
Error at channel 0
0
Error at channel 1
0
Error at channel 2
0
Error at channel 3
0
Error at channel 4
0
Error at channel 5
0
Error at channel 6
0
Error at channel 7
0
Reserved
0
Channel 0 error
to
Channel 7 error
0
0
Parameter Error
0
1
Overload
0
2
Reserved
0
3
Fuse blown
0
4
Line break
0
5
Reserved
0
6
Lower limit exceeded
0
7
Upper limit exceeded
0