User Manual Section 3
GFK-2958L May 2021
Configuration 32
Module 11 (without power refresh):
I = 8.19 A + (0.015 A + (0.5 A x 4) = 10.205 A
Therefore, the available 10 A would be exceeded. As a result, an EP-7641 power supply
module must be positioned as the 11
th
module, which will supply the required power to the
subsequent modules after the power feed module. Unused current values may not be
included.
Module 11 (as per PF-O):
I = (0.015 A + (0.5 A x 4) = 2.015 A
Module 12 (as per PF-O):
I = 2.015 A (0.015 A + (0.5 A x 4) = 4.030 A
3.7 Example Calculation for the Current Demand
(all Current Values in Amps)