User Manual Appendix D
GFK-2958L May 2021
Product Certifications and Installation Guidelines for Conformance 524
D.1 UL Class 1 Division 2 Hazardous Areas Requirements
The following statements are required to display for Class I Division 2 Hazardous Locations:
1. EQUIPMENT LABELED WITH REFERENCE TO CLASS I, GROUPS A, B, C, and D, DIV. 2 HAZARDOUS
LOCATIONS IS SUITABLE FOR USE IN CLASS I, DIVISION 2, GROUPS A, B, C, D OR NON
HAZARDOUS LOCATIONS ONLY.
2. WARNING EXPLOSION HAZARD SUBSTITUTION OF COMPONENTS MAY IMPAIR SUITABILITY
FOR CLASS I, DIVISION 2.
3. WARNING EXPLOSION HAZARD DO NOT DISCONNECT EQUIPMENT UNLESS POWER HAS BEEN
SWITCHED OFF OR THE AREA IS KNOWN TO BE NONHAZARDOUS.
4. EQUIPMENT SHALL BE INSTALLED INTO AN ENCLOSURE THAT IS ONLY ACCESSIBLE WITH THE USE
OF A TOOL
D.2 ATEX Zone 2 Hazardous Areas Requirements
To maintain compliance with the ATEX Directive, an RSTi-EP system located in a Zone 2 area (Category
3) must be installed within a protective enclosure meeting the following criteria:
IP54 or greater
Mechanical strength to withstand an impact energy of 3.5 Joules
Only accessible with the use of a tool