262
Control function
● When DSW4-5 is ON, pump of WP1/WP3 is in Economic mode, water pump works as shown in the graphic below:
Space heating
t1
2min/t1
2min
t2
t1
t2
t1
Switch
ON/OFF
Thermo
ON/OFF
WP3
ON
OFF
ON
OFF
ON
OFF
WP1
ON
OFF
t1
2min/t1
2min
t2
t1
t2
t1
Switch
ON/OFF
Thermo
ON/OFF
WP3
ON
OFF
ON
OFF
ON
OFF
WP1
ON
OFF
Space cooling
The conguration of this option should be done through the master controller.
Conguration →Heat pump→ Water pump conguration,
Mark Description Default Value Range Steps Units
tPumpOFF Min. ON Time 40 0-120 10 min
tPumpON Min. OFF Time 10 0-20 2 min
t1= tPumpON
t2= tPumpOFF