100 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Parts of the H-S81-HS System Termination modules
Field Connections
2.5.7 S81-T8007-1
Description
It is used with S81-E2001-1
and S81-F5002-1 type
buses. It features 16 x 4A
30VDC SPDT output con-
tacts to be used for the con-
nection of SELV circuits
only. It is also used together
with the S81-T8004-1 mod-
ule.
Technical Features
Status Indications
The module includes 16 green LEDs for relay status indication:
NC= Normally Closed
NO= Normally Open
COM= Common
Relays
K1 K2 K3 K4 K5 K6 K7 K8
NC
NO
COM
NC
NO
COM
NC
NO
COM
NC
NO
COM
NC
NO
COM
NC
NO
COM
NC
NO
COM
NC
NO
COM
BR1 1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
CAUTION: EN-54-2 COMPLIANCE
THE OUTPUTS ABOVE ARE NOT C-, E- OR J-TYPE OUTPUTS (EN 54-1), THEREFORE THEY
MUST NOT BE USED TO CONTROL FIRE ALARM DEVICES OR ALARM, FIRE ALARM OR
FAULT ALARM TRANSMISSION DEVICES. THIS GUARANTEES COMPLIANCE WITH
STANDARD EN-54-2.
• Supply voltage: 22-29VDC
• Quiescent current: 0 mA
• Contact type: SPDT
• Contact capacity: 4 A 30VDC
• Assembly: on DIN bar
• Operating temperature: -5 - 50 °C
• Storage temperature: -30 - 80 °C
• Maximum humidity: 95% non-condensing
• Dimensions: W 170 x H 77 x D 50 mm
LED Condition
LED1 - LED16 (Green LEDs) It lights up when relay coil is active