H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 101
Termination modules Parts of the H-S81-HS System
Field Connections
2.5.8 S81-T8007-2
Description
This module is used together with module
S81-F5003-1 and allows to control up to 4 sound-
ers with a maximum absorption of 2A each.
Technical Features
Status Indications
The module includes 4 green LEDs for output status indication:
Internal Connections
BR1 Terminal Block
2-way terminal block for power supply connection.
SPDT contacts
NC = Normally closed
NO = Normally open
COM = Common
K1 K2 K3 K4 K5 K6 K7 K8
NC
NO
COM
NC
NO
COM
NC
NO
COM
NC
NO
COM
NC
NO
COM
NC
NO
COM
NC
NO
COM
NC
NO
COM
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
BR1
K9 K10 K11 K12 K13 K14 K15 K16
NC
NO
COM
NC
NO
COM
NC
NO
COM
NC
NO
COM
NC
NO
COM
NC
NO
COM
NC
NO
COM
NC
NO
COM
1 2 3 4 5 6 7 8 9 10 11 12 13 14 15 16 17 18 19 20 21 22 23 24
BR2
CAUTION: EN-54-2 COMPLIANCE
THE OUTPUTS ABOVE ARE NOT C-, E- OR J-TYPE OUTPUTS (EN 54-1), THEREFORE THEY
MUST NOT BE USED TO CONTROL FIRE ALARM DEVICES OR ALARM, FIRE ALARM OR
FAULT ALARM TRANSMISSION DEVICES. THIS GUARANTEES COMPLIANCE WITH
STANDARD EN-54-2.
• Supply voltage: 22-29VDC
• Quiescent current: 0mA
• Max. output current 2A - current protected
• Assembly: on DIN bar
• Operating temperature: -5 - 50 °C
• Storage temperature: -30 - 80 °C
• Maximum humidity: 95% (RH) non-condensing
• Dimensions: W 78 x H 77 x D 50 mm
LED Condition
LED1 - LED4 (Green LEDs) They light up when outputs are active
Tag Function Notes
∅ M1 25VDC power supply positive Red
∅ M2 25VDC power supply negative Black