98 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Parts of the H-S81-HS System Termination modules
Field Connections
BR1 Terminal Block
It is a 12-way terminal block to connect the ten default inputs and the local fire alarm sounder.
M11 K11 Currently not used
System
Normally energized
M12 K12 Running System Normally energized
M13 K13 System fault Normally energized
M14 K14 Power supply fault Normally energized
M15 K15 CPU fault Normally energized
M16 K16 Control panel reset Pulsing on reset
BR1 Function Type Notes
M1 Remote buzzer silencing input Safety N.O.
M2 Remote sounder silencing input Safety N.O.
M3 Remote control panel reset input Safety N.O.
M4 Remote evacuation control input Safety N.O.
M5 Battery status input (supply/charge) System 0V during charge
M6 PSU1 primary power supply trouble input System N.C.
M7 PSU2 secondary power supply trouble input System N.C.
M8 Battery charge status (Full charge/Trickle) System 0V full charge
M9 External Fault Input Safety N.C
M10 Revolving door tamper input Security N.C
M11 Local sounder/buzzer output + Safety max. 250mA
M12 Local sounder/buzzer output - Safety max. 250mA
!
CAUTION: EN-54-2 COMPLIANCE
THE REMOTE EVACUATION CONTROL AND REMOTE CONTROL PANEL RESET INPUTS
MUST NOT BE ACTUATED DIRECTLY THROUGH EXTERNAL MANUAL BUTTONS SINCE THEY
ARE NOT MONITORED. THIS GUARANTEES COMPLIANCE WITH STANDARD EN-54-2.

Table of Contents

Other manuals for Honeywell H-S81-HS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell H-S81-HS and is the answer not in the manual?

Honeywell H-S81-HS Specifications

General IconGeneral
BrandHoneywell
ModelH-S81-HS
CategoryControl Panel
LanguageEnglish

Related product manuals