98 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Parts of the H-S81-HS System Termination modules
Field Connections
BR1 Terminal Block
It is a 12-way terminal block to connect the ten default inputs and the local fire alarm sounder.
∅ M11 K11 Currently not used
System
Normally energized
∅ M12 K12 Running System Normally energized
∅ M13 K13 System fault Normally energized
∅ M14 K14 Power supply fault Normally energized
∅ M15 K15 CPU fault Normally energized
∅ M16 K16 Control panel reset Pulsing on reset
BR1 Function Type Notes
∅ M1 Remote buzzer silencing input Safety N.O.
∅ M2 Remote sounder silencing input Safety N.O.
∅ M3 Remote control panel reset input Safety N.O.
∅ M4 Remote evacuation control input Safety N.O.
∅ M5 Battery status input (supply/charge) System 0V during charge
∅ M6 PSU1 primary power supply trouble input System N.C.
∅ M7 PSU2 secondary power supply trouble input System N.C.
∅ M8 Battery charge status (Full charge/Trickle) System 0V full charge
∅ M9 External Fault Input Safety N.C
∅ M10 Revolving door tamper input Security N.C
∅ M11 Local sounder/buzzer output + Safety max. 250mA
∅ M12 Local sounder/buzzer output - Safety max. 250mA
CAUTION: EN-54-2 COMPLIANCE
THE REMOTE EVACUATION CONTROL AND REMOTE CONTROL PANEL RESET INPUTS
MUST NOT BE ACTUATED DIRECTLY THROUGH EXTERNAL MANUAL BUTTONS SINCE THEY
ARE NOT MONITORED. THIS GUARANTEES COMPLIANCE WITH STANDARD EN-54-2.