H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 79
I/O modules Parts of the H-S81-HS System
Supported Devices
This module can control the following types of addressable devices:
2.4.13 S81-F7009-1
Description
Control module for addressable devices using XP95/Discovery Apollo protocol.
This module can control up to a maximum of 127 fire detection modules includ-
ing: smoke, heat, combined detectors, alarm buttons, control modules, visual
and audible alarm devices.
Technical Features
Status Indications
The front panel includes 8 LEDs with the following functions:
Part Number Description Type Pros-81 Notes
S81-Mod-DI Module with 8 non monitored inputs DI Requires external power supply
S81-Mod-AIT Module with 4 monitored inputs AIT Requires external power supply
S81-Mod-AI020 Module with 1 x 4-20 mA input AI020 Requires external power supply
S81-Mod-AV010 Module with 1 x 0-10V input AV010 Requires external power supply
S81-Mod-DO Module with 8 open collector outputs DO Requires external power supply
S81-Mod-DISP 255 message display module DISP Requires external power supply
1
1 A maximum of 64 modules can be installed in a loop.
• Redundancy: No
• Number of devices per loop: 127
• Loop maximum current: 400mA
• Supply voltage: 22-29VDC
• Quiescent current: 90mA
• Operating temperature: -5 - 50 °C
• Storage temperature: -30 - 80 °C
• Maximum humidity: 95% (RH) non-condensing
• Hot swap capability: yes
LED Indication
Active (Red LED) Steady on if an input is under alarmed/activated condition
Disabled (Yellow LED) Steady on if an input or an output is disabled
Fault (Yellow LED) Flashing in case of Fault condition
Loop Fault (Yellow LED) Flashing in case of loop short circuit or open loop
Log on Fault (Yellow LED) Flashing in case of difference between the detected devices and the programmed ones.
Service (Yellow LED) Flashing in case of in case of smoke detectors with dirty lenses
TX Pol. (Green LED) It lights up every time data are transmitted from the module to loop devices.
RX Pol. (Green LED) It lights up every time data from loop devices are received

Table of Contents

Other manuals for Honeywell H-S81-HS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell H-S81-HS and is the answer not in the manual?

Honeywell H-S81-HS Specifications

General IconGeneral
BrandHoneywell
ModelH-S81-HS
CategoryControl Panel
LanguageEnglish

Related product manuals