EasyManuals Logo

Honeywell H-S81-HS User Manual

Honeywell H-S81-HS
176 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #19 background imageLoading...
Page #19 background image
H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 19
Safety and Availability of the H-S81-HS System General Description
1.3.6 Electromagnetic Compatibility (CE)
The H-S81-HS system has been designed and tested for resisting to standard levels of radiated and
conducted electromagnetic interference, and electrostatic discharges. The table below lists the types
and levels of the tests undergone by the H-S81-HS system.
1.4 Safety and Availability of the H-S81-HS System
The H-S81-HS system is intended for use in applications requiring a high safety level, together
with high system availability. According to the required safety and availability levels, different
H-S81-HS system configurations can be provided.
1.4.1 Possible Configurations of the H-S81-HS System
“Mono” Configuration
This solution includes the duplicated central unit and the I/O modules in a single configuration.
Basic Standard Date Title Noise Immunity Tests
EN 61000-4-2
A1
A2
1995
1998
2001
Electrostatic discharge immunity test
6 kV contact discharge
8 kV air discharge
EN 61000-4-3
A1
A2
1996
1998
2001
Radiated, radio-frequency, electromagnetic
field immunity test
10 V/m, 80 MHz-2 GHz, 80% AM
EN 61000-4-4
A1
A2
1995
2001
2001
Electrical fast transients/bursts immunity test
2 kV power supply
1 kV signal lines
EN 61000-4-5
A1
1995
2001
Surge immunity test
2 kV common mode
1 kV differential mode
ENV 50141 1994 Conducted disturbances induced by radio-
frequency fields immunity test
10 V, 150 kHz-80 MHz, AM
EN 61000-4-11
A1
1994
2001
Voltage dips, short interruptions and voltage
variations immunity test
60% 200ms
100% 100ms
!
CAUTION: ELECTROMAGNETIC COMPATIBILITY
ELECTRICAL DISTURBANCES VARY SIGNIFICANTLY ACCORDING TO THE TYPE OF
INSTALLATION AND WIRING DISTANCE TO AND FROM OTHER DEVICES. THEREFORE, IT IS
IMPORTANT TO MAKE SURE THAT THE ELECTROMAGNETIC INTERFERENCE LEVELS DO
NOT EXCEED THE VALUES REPORTED IN THIS TABLE.
Figure 1.3 “Mono” Configuration

Table of Contents

Other manuals for Honeywell H-S81-HS