H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015 17
General Features General Description
1.3 General Features
1.3.1 Mechanical Properties
H-S81-HS/1R
H-S81-HS/2R
H-S81-HS/1-10R
• Serial communication interface: 2 x RS232
• Ethernet communication interface: 10/100BaseT with RJ45 connector
• Maximum number of programmable zones: 300 fire alarm zones + 300 burglar alarm zones
• Maximum number of programmable points per zone: 99 inputs 99 outputs 99 links
• Exportable local variables via network: Max. 250
• Importable remote variables via network: Max. 999
• System variables (Local): 64
• Maximum number of modules: 130 (10 rack version)
• Time slots with holiday management: 10 (with 10 intervals each)
• CPU redundancy: Optional
• I/O bus redundancy: Optional
• Module redundancy: Optional only for safety related modules
• Hot swap capability: Available for all modules
• Centralization between control panels: Via LAN network with RCP protocol
• Supervisory system: Max. three supervisors per control panel
• Management of time slots: 10 categories with management of holidays
• Default outputs: 16 SPDT contacts
• Default inputs: 10 opto-isolated inputs
• Available protocols: MODBUS RTU
NOTE: In order to comply with the requirements of EN54-2 standard, a maximum of 32
detectors and/or fire alarm buttons can be set in each zone of the area-1.
• Steelwork type Metal, with transparent door and revolving inner door
• Color RAL 7035
• Protection class IP30
• Type of installation Wall installation
• Dimensions H=700mm W=600mm D=400mm
• Steelwork type Metal, with transparent door and revolving inner door
• Color RAL 7035
• Protection class IP30
• Type of installation Wall installation
• Dimensions H=1100mm W=600mm D=400mm
• Steelwork type: Metal, with transparent door and revolving inner door
• Color: RAL 7032
• Protection class: IP30
• Type of installation: Floor ground installation
• Dimensions: H=2100mm W=800mm D=800mm