32 H-S81-HS Installation & Operation Manual — P/N LS10114-000HI-E:A 2/24/2015
Parts of the H-S81-HS System Power Supply Set
Technical Features
Power Supply Unit Section
Battery Charger Section
Cooling Unit
Protections
Reference Standards
EN54-4
EN50081-2
EN50082-2
EN60950 (CEI-74-2)
Dimensions (H x W x D): 178 x 482 x 355mm
Input voltage: 110-240V~ (-15% - 10%)
Max. input current: See tab.1
Free-air operating temperature: -5 °C - 50 °C
Relative humidity: 93% non-condensing
Input voltage frequency: 50-60 Hz
Power factor (W/VA): 0.6 Typical
Protection class: IP20
Insulation between input and output: >2 M Ω (500VDC)
Insulation between input and ground: >2 M Ω (500VDC)
VLOAD voltage: 25VDC ±2%
VLOAD maximum current: 32A duplicated
VLOAD ripple: < 110mV pK-pK at maximum current
Battery voltage: 26.2 - 28.7 VDC compensated automatically
Resistance to mains voltage dips: >=20mS at maximum current
Maximum battery current: 6A
Maximum battery resistance:
Internal resistance of the batteries and of the relevant circuits
(Cables, terminals, fuses, etc.)
Type of cooling Forced ventilation (3 fans)
Fan absorption 100mA per fan
Fan average life at 40° C 80,000 hours
Line Fuse: T10A H 250V (5x20)
Protections: Over-voltage, short circuit and battery reverse polarity

Table of Contents

Other manuals for Honeywell H-S81-HS

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell H-S81-HS and is the answer not in the manual?

Honeywell H-S81-HS Specifications

General IconGeneral
BrandHoneywell
ModelH-S81-HS
CategoryControl Panel
LanguageEnglish

Related product manuals