Function Prompt
Selections or Range of
Setting
Parameter Definition
Low Select
(See Note 2)
Input Low Select with Ratio and
Bias This selection specifies the
PV or SP as the lower of Input 1 or
Input 2. The following formula
applies:
Alg1 = lower of (Input A x Ratio A +
Bias A) or (Input B x Ratio B + Bias
B)
Multi Div + Sqrt
(See Note 1)
Multiplier Divider with Square Root
—The following formula applies:
Alg1 = K * Sq.Rt. {(Input A x Ratio A +
Bias A) x (Input C x Ratio C + Bias C)
/ (Input B * Ratio B + Bias B)} x (Calc
Hi Calc Lo) + Alg1Bias
See the figure at the end of this
section for an example of Mass Flow
Compensation using the
Multiplier/Divider Algorithm.
Multiplier + Sqrt
(See Note 1)
Multiplier with Square Root —The
following formula applies:
Alg1 =K x Sq.Rt.{(Input A x Ratio A +
Bias A) x (Input B x Ratio B + Bias B)
x (Input C x Ratio C + Bias C)} x
(Calc Hi Calc Lo) + Alg1Bias
Multiplier Divider
(See Note 1)
Multiplier Divider The following
formula applies:
Alg1 = K x [{(Input A x Ratio A + Bias
A) x (Input C x Ratio C + Bias C)} /
(Input B x Ratio B + Bias B)] x (Calc
Hi Calc Lo) + Alg1Bias
Multiplier
(See Note 1)
Multiplier —The following formula
applies:
Alg1 = K x [(Input A x Ratio A + Bias
A) x (Input C x Ratio C + Bias C) x
(Input B x Ratio B + Bias B)] x (Calc
103
Chapter 4 - Configuration

Table of Contents