Function
Prompt
Selections or Range
of Setting
Parameter Definition
algorithms, it may be used to perform an
Auxiliary Output function.
Disable Disable
Input 1 Input 1
Input 2 Input 2
PV Process Variable
Deviation Deviation
Output Output
SP Setpoint
Local SP 1 Local Setpoint 1
Local SP 2 Local Setpoint 2
Local SP 3 Local Setpoint 3
Local SP 4 Local Setpoint 4
Remote SP Remote Setpoint
Input Algorithm 1 Input Algorithm 1
CO Low
Value
Low Scale Value
within the range of
the selected variable
to represent the
minimun output (0
or 4 mA)
Current Output Low Scaling Factor —Used
only when CUR OUT is any selection other
than DISABLE. This is a value in engineering
units used to represent all CUR OUT
parameters except Output.
For Output, this is a value in percent and can
be any value between –5 % and +105 %.
However, keep in mind that relay output types
can only be scaled 0 % to 100 %.
CO High
Value
High Scale Value
within the range of
the selected variable
to represent the
maximum output
(20 mA)
Current Output High Scaling Factor —Used
only when CUR OUT is any selection other
than DISABLE. This is a value in engineering
units used to represent all CUR OUT
parameters except Output.
For Output, this is a value in percent and can
be any value between –5 % and +105 %.
113
Chapter 4 - Configuration