134
Function
Prompt
Selections or Range
of Setting
Parameter Definition
Enable Allows output rate.
Disable Disables output rate.
Rate Up %
Min
0 to 9999 % per
minute
Output Rate Up Value- This selection limits the
rate at which the output can change upward.
Enter a value in percent per minute. Appears
only if OUT RATE is enabled. “0” means no
output rate applied.
Rate Down
% Min
0 to 9999 % per
minute
Output Rate Down Value- This selection limits
the rate at which the output can change
downward. Enter a value in percent per
minute. Appears only if OUT RATE is enabled.
“0” means no output rate.
Output High
Limit
High Output Limit- This is the highest value of
output beyond which you do not want the
controller automatic output to exceed.
0 % to 100 % For relay output types.
–5 % to 105 % For current output types.
Output Low
Limit
Low Output Limit- This is the lowest value of
output below which you do not want the
controller automatic output to exceed.
0 % to 100 % For relay output types.
–5 % to 105 % For current output types.
Integral High
Limit
(Note 5)
Within the range of
the output limits
High Reset Limit- This is the highest value of
output beyond which you do not want reset
action to occur
Integral Low
Limit
(Note 5)
Within the range of
the output limits
Low Reset Limit- This is the lowest value of
output beyond which you do not want reset
action to occur.
Dropoff
(Note 5)
–5 to 105 % of
output
Controller Dropoff Value- Output value below
which the controller output will drop off to the
low output limit value set in prompt Output
Low Limit.
Chapter 4 - Configuration