Miscellaneous Features
Auxiliary Output*(optional): Either or both of the two current outputs
can function as an Auxiliary Output which can be scaled from 0-20
mA or 4-20 mA for 0 to 100% for any range. It can be configured to
represent Input 1, Input 2, PV, active Setpoint, Local SP1, Deviation,
or the Control Output.
Transmitter Power: This output provides up to 28 volts DC to power a
2-wire transmitter (it requires the use of Open Collector Output
(Transmitter Power Output) selection or the Auxiliary Output).
Four Local and one Remote Setpoints: Can be configured to provide four
Local and one Remote Setpoints, which are selectable either via the
keyboard or by Digital Input.
Universal Switching Power: Operates on any line voltage from 90 to 264
Vac 50/60 Hz without jumpers. 24 Vac/dc instrument power,
powered by a power supply which provides double/reinforce
insulation or Safety Extra-low Voltage Circuit (SELV) Input, is
available as an option.
Timer: This standard feature provides a configurable time period of 0
to 99 hours, 59 minutes or units of minutes and seconds. It can be
started via the keyboard, alarm 2, or by a digital input. The timer
output is Alarm 1, which energizes at the end of the Timer Period.
Alarm 1 can be automatically reset. The Timer Period can be changed
between each batch. Status is shown on the lower display.
Moisture Protection: The NEMA4X and IP66 rated front face permits
use in applications where it may be subjected to moisture, dust, or
hose-down conditions.
Setpoint Ramp/Soak Programming (Optional): Enables you to use 8
programs and store 4 Ramp and 4 Soak segments per program.
Program can be linked up to 64 segments. Run or Hold of program is
keyboard or remote digital switch selectable.
Setpoint Rate: Lets you define a ramp rate to be applied to any local
setpoint change. A separate upscale or downscale rate is
configurable. A single setpoint ramp is also available as an
alternative.
CE Mark: Conformity with Radio Equipment Directive 2014/53/EU.
Radio Compliance information:
Federal Communications Commission (FCC) contains FCC ID:
2AVFQ-MCUDISP;
Industry Canada (IC) contains IC: 25762-MCUDISP.
18
Chapter 2 - Introduction

Table of Contents

Other manuals for Honeywell UDC2800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell UDC2800 and is the answer not in the manual?

Honeywell UDC2800 Specifications

General IconGeneral
Control ModesPID, ON/OFF, Manual
MountingPanel Mount
DisplayDual 4-digit LED
Input TypesThermocouple, RTD, mA, mV, V
Output TypesRelay
Power Supply100-240 VAC, 50/60 Hz
CommunicationRS-485 Modbus RTU
Enclosure RatingNEMA 4X