Step Operation Press Result
2 Go to Error
Code Prompt
Function key, and
Increment or
Decrement key
Enter in Error Code prompt. Table below
lists all the error codes, definitions, and
fixes.
Table 5-13: Accutune Error Codes
Error
Code
Definition Fix
NONE No errors occurred during last
accutune procedure
None
Running Accutune running The Accutune process is still active (Read
Only)
Abort Current Accutune Process
Aborted caused by the
following conditions:
a. Operator changed to
Manual mode
b. Digital Input detected
c. In Heat region of output and
a Cool output calculated or
vice versa.
Try Accutune again
SP Error
LSP2 not enabled or LSP1 or
LSP2 not in use (only applies
to Duplex Tuning)
Enable LSP2 and configure the desired
LSP1 and LSP2 setpoints. See Accutune
III for more information.
Aborting Accutune
To abort Accutune and return to the last previous operation (SP or
output level), press Man Auto key to abort the Accutune process or
increment from the “SLOW” or “FAST” prompt to the “TUNE OFF”
prompt.