Program Contents
It lists all the program contents and a description of each.
Table 5-22: Program Contents
Associated
Prompts
Contents Definition
Start Segment Start segment
number
The start segment number designates the
number of the first segment.
Range = 1 to 8
End Segment End segment
number
The end segment number designates the number
of the last segment, it must be a soak segment
(even number).
Range = 2 to 8
Recycles Recycle
number
The recycle number allows the program to recycle
a specified number of times from beginning to
end.
Range = 0 to 99
Program End State Program state The program state selection determines the
program state after completion.
The selections are:
• Disable: SP Program Function is disabled (so
program value changed to Disable).
• Hold: SP Program Function is not disabled.
Program
Termination
Program
termination
state
The program termination state function
determines the status of the controller upon
completion of the program.
The selections are:
• Last SP: controls to last setpoint
• Failsafe: manual mode and failsafe output.
Key Reset/Rerun To Begin Reset Program to Beginning. Press the Lower
Display key under the main screen, until you see
To Begin, then press the Increment key or
Decrement key, To Begin will go into effect.
217