EasyManuals Logo

Honeywell UDC2800 User Manual

Honeywell UDC2800
432 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Page #242 background imageLoading...
Page #242 background image
242
Calibrator Connections
Refer to figure below and wire the controller according to the
procedure given in the table.
Figure 7-1: Wiring Connections for Calibrating Current Proportional
Output
Table 7-1: Set Up Wiring Procedure for Current Output
Step Action
1 Apply power and allow the controller to warm up 30 minutes before you
calibrate.
2 Set Lockout in the Security set up group to None.
3 Tag and disconnect the field wiring, at the rear of the controller, from terminals
21 (–) and 19 (+). Seefigure below.
4 Connect a milliammeter across these terminals.
Procedure
The procedure for calibrating the Current Output is listed in table
below.
Make sure Lockout in the Security set up group is set to None. See
Security Set Up Group for more information.
Chapter 7 - Output Calibration

Table of Contents

Other manuals for Honeywell UDC2800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell UDC2800 and is the answer not in the manual?

Honeywell UDC2800 Specifications

General IconGeneral
Control ModesPID, ON/OFF, Manual
MountingPanel Mount
DisplayDual 4-digit LED
Input TypesThermocouple, RTD, mA, mV, V
Output TypesRelay
Power Supply100-240 VAC, 50/60 Hz
CommunicationRS-485 Modbus RTU
Enclosure RatingNEMA 4X

Related product manuals