SP Program 8
Table below lists all the register addresses and ranges or selections
for the function parameters in Set-up Group SP Program 8.
Table 11-23: Set-up Group Setpoint Program 8
Parameter Description
Register Address
Data
Type
Access
Data Range or
Enumerated
Selection
Hex Decimal
SP Program 8 865 2149 INT
R/W
0 = Disabled
1 = Enabled
Start Segment 866 2150 INT
R/W
Ramp segment
1 to 8
End Segment 867 2151 INT
R/W
Soak segment
0 = Soak 8
1 = Soak 6
2 = Soak 4
3 = Soak 2
Ramp Unit 868 2152 INT
R/W
0 = Time Hrs:Mins
1 = Rate EU/Mins
2 = Rate EU/Hrs
Recycles 869 2153 INT
R/W
0 to 100
Segment 1 Ramp AB 171 FP
R/W
99.59 (0-99 Hrs:0
-59Min) or
0 to 999
(Degrees/Minute)
Segment 2 SP AC 172 FP
R/W
Within Setpoint
Limits
Segment 2 Time AD 173 FP
R/W
99.59 (0-99 Hrs:0
-59Min)
Segment 3 Ramp AE 174 FP
R/W
99.59 (0-99 Hrs:0
-59Min) or
0 to 999
(Degrees/Minute)
Segment 4 SP AF 175 FP
R/W
Within Setpoint
Limits
Chapter 11 - Modbus RTU Function Codes 20&21