Parameter Description
Register
Address
Data
Type
Access
Data Range or
Enumerated Selection
Hex Decimal
Accutune Duplex
selection
871 2161 INT
R/W
0 = Manual
1 = Auto
2 = Disable (blend)
Accutune Error Status
(Read only)
872 2162 INT
R
0 = None
1 = Running
1 = Abort
3 = SP Error
Algorithms
The following table lists all the register addresses and ranges or
selections for the function parameters in Set-up Group Algorithm.
Table 11-25: Set-up Group Algorithm
Parameter Description
Register Address
Data
Type
Access
Data Range or
Enumerated
Selection
Hex Decimal
Control Algorithm
Selection (Selection
here will affect ID code
39 in Output
Algorithms.)
87B 2171 INT
R/W
0 = Disable
1 = On-Off
2 = PID A
3 = PID B
4 = PD-A with
Manual Reset
5 = Three Position
Step
Timer Function 87C 2172 INT
R/W
0 = Disable
1 = Enable
Period Hrs:Mins BF 191 FP
R/W
00.00 TO 99.59
Start Trigger 87D 2173 INT
R/W
0 = Keyboard
(Run/Hold by
Chapter 11 - Modbus RTU Function Codes 20&21