356
Parameter
Description
Register
Address
Data
Type
Access
Data Range or
Enumerated
Selection
Hex Decimal
24 = Linear
25 = Square Root
Input 1 High
Value
CE 206 FP
R/W
–999. to 9999.
Engineering Units
(Linear types only)
Input 1 Low Value CF 207 FP
R/W
–999 to 9999.
Engineering Units
(Linear types only)
Input 1 Ratio D0 208 FP
R/W
–20.00 to 20.00
Input 1 Bias D1 209 FP
R/W
–999 to 9999.
Engineering Units
Input 1 Filter D2 210 FP
R/W
0 to 120 seconds
Input 1 Burnout
(Open Circuit
Detection)
89B 2203 INT
R/W
0 = No Burnout
1 = Upscale Burnout
2 = Downscale
Burnout
3 = No Failsafe
Input 2
Table below lists all the register addresses and ranges or selections
for the function parameters in Set-up Group Input 2.
Table 11-28: Set-up Group Input 2
Parameter
Description
Register Address
Data
Type
Access
Data Range or
Enumerated
Selection
Hex Decimal
Input 2 Type 89E 2206 INT R/W 0 = Disable
1 = TC B
Chapter 11 - Modbus RTU Function Codes 20&21

Table of Contents