382
Parameter Description
Register Address
Access Description
Hex Decimal
integer, prescale *
10 ( Note 1)
Output Override Value 0022 40035
R/W Signed 16 bit
integer, prescale *
10
Ratio, CSP parameters 0023 40036
R/W Signed 16 bit
integer, prescale *
10
Bias, CSP parameters 0024 40037
R/W Signed 16 bit
integer, prescale *
10
Deviation 0025 40038
R Signed 16 bit
integer, prescale *
10
LSP #3 0026 40039
R/W Signed 16 bit
integer, prescale *
10
Percent Carbon Monoxide
- CO
0027 40040
R/W Signed 16 bit
integer, prescale
*1000
Decimal Point 0028 40041
R/W Signed 16 bit
integer, prescale *1
Alg1 Bias 0029 40042
R/W Signed 16 bit
integer, prescale *10
( Note 2)
LSP #4 002B 40044
R/W Signed 16 bit
integer, prescale *
10 ( Note 1)
Current Output #2 002C 40045
R Signed 16 bit
integer, prescale *
10 ( Note 1)
Fuzzy Enable 0038 40057
R/W Unsigned 16 bit
integer
0=Disable
Chapter 12 - Standard Modbus Read, Write and Override Parameters