Parameter Description
Register Address
Access Description
Hex Decimal
in Seconds or
Time Units
Status 1E5B 47772
R Bit 0: 1=Ready
1: 1=Run
2: 1=Hold
3: 1=End
4: 1=Time Units
in Seconds
5: 1=Time Units
in Minutes
6: 1=Time Units
in Hours
7: Ramp Units
l
0: Time
l
1: Rate
8: If bit 7 Set
l
0: EU/Hour
l
1:
EU/Minute
9: Guaranteed
Soak State
Start 1E5C 47773
W Signed 16 bit
integer
Write to
location Starts
Profile;
Data ignored
Hold 1E5D 47774
W Signed 16 bit
403
Chapter 12 - Standard Modbus Read, Write and Override Parameters