Function Prompt
Selections or Range of
Setting
Parameter Definition
End Segment 2 to 8 even numbers Always
end in a soak segment (2, 4, 6
and 8)
End Segment Number
Ramp Unit Engineering Units for Ramp
Segments
Time Hrs:Mins Time in hours: minutes
Rate EU/Mins Rate in Engineering units
per minute
Rate EU/Hrs Rate in Engineering units
per hour
Recycles 0 to 99 recycles Number of Program
Recycles
Segment 1 Ramp 00:00 ~ 99:59 (0-99 hours:0-
59 minutes)
or
0 ~ 999 EU/Min
or
0 ~ 999 EU/Hr
Segment #1 Ramp
Time/Rate
NOTE: This
parameter is affected
by the Ramp Unit
configuration. Select
Time Hrs:Mins , Rate
EU/Mins, or Rate
EU/Hrs at prompt
Ramp Unit. All ramps
in this SP Program
will use the same
selection.
Segment 2 SP Within the Setpoint limits Segment #2 Soak Setpoint
Value
Segment 2 Time 00:00 ~ 99:59 (0-99 hours:0-
59 minutes
Segment #2 Soak Duration
Segment 3 Ramp
Segment 4 SP &
Segment 4 Time
Segment 5 Ramp
Selections are same as above. Same as above
89
Chapter 4 - Configuration

Table of Contents

Other manuals for Honeywell UDC2800

Questions and Answers:

Question and Answer IconNeed help?

Do you have a question about the Honeywell UDC2800 and is the answer not in the manual?

Honeywell UDC2800 Specifications

General IconGeneral
Control ModesPID, ON/OFF, Manual
MountingPanel Mount
DisplayDual 4-digit LED
Input TypesThermocouple, RTD, mA, mV, V
Output TypesRelay
Power Supply100-240 VAC, 50/60 Hz
CommunicationRS-485 Modbus RTU
Enclosure RatingNEMA 4X

Related product manuals