Parameter Name / value range / [default seng] Info
0x400E:016
(PAR 505/016)
NETWordIN1 funcon assignmen
t: Bit 15
(NETWordIN1 cong.: NETWordIN1.15)
Seng can only be changed if controller inhibit is
acve.
For possible sengs see descripon for 0x400E:
001 (PAR 505/001).
^ 98
Denion of the funcon tha
t is to be triggered via bit 15 of the mappa-
ble NETWordIN1 data word.
00 Not acve Trigger bit without any funcon.
0x2022:027
(PAR 700/027)
Device commands: Accept new inverter hardware
(Device commands: Accept new HW)
0 ... [0] ... 1
Seng can only be changed if controller inhibit is
acve.
1 = inialise parameters for a new network opon.
0x2631:037
(PAR 400/037)
Funcon assignment: Network enable
(Funcon list: Network enable)
For possible sengs see descripon for
0x2631:001 (PAR 400/001). ^ 188
Assignment of a trigger for the "Network enable" funcon.
Trigger = TRUE: acvate network control mode.
Trigger = FALSE: no acon / deacvate network control mode again.
00 Not connected No trigger assigned (trigger is constantly FALSE).
0x2860:001
(PAR 201/001)
Standard setpoint sources: Frequency setpoint source
(Standard setpoint: Frequency setp.)
For possible sengs see descripon for
0x2860:001 (PAR 201/001). ^ 70
Selecon of the standard setpoint source for speed mode.
The standard setpoint source is always acve in speed mode if no set-
point change-over to another setpoint source via corresponding trig-
gers/funcons is acve.
4Setpoint change-over ^ 193
2 Analog input 1 The se
tpoint is specied analogously via X3/AI1.
4Analog input 1 ^ 211
0x2860:002
(PAR 201/002)
Standard setpoin
t sources: Process controller setpoint
source
(Standard setpoint: PID setpoint)
For possible sengs see descripon for
0x2860:002 (PAR 201/002). ^ 70
Selecon of the standard setpoint source for process controller mode.
The standard setpoint source is always acve in process controller
mode if no setpoint change-over to another setpoint source via corre-
sponding triggers/funcons is acve.
1 Keypad The setpoint is specied locally by the keypad.
Default seng: 0x2601:002 (PAR 202/002)
Use the
and
navigaon k
eys to change the keypad setpoint
(also during running operaon).
0x2860:003
(P
AR 201/003)
St
andar
d setpoint sources: Torque setpoint source
(Standard setpoint: Torque setp.)
Selecon of the standard setpoint source for torque mode.
The standard setpoint source is always acve in torque mode if no
setpoint change-over to another setpoint source via corresponding
triggers/funcons is acve.
1 Keypad The setpoint is specied locally by the keypad.
Use the
and
navigaon k
eys to change the keypad setpoint
(also during running operaon).
2
Analog input 1 The se
tpoin
t is specied analogously via X3/AI1.
4Analog input 1 ^ 211
3 Analog input 2 The setpoint is specied analogously via X3/AI2.
4Analog input 2 ^ 213
50 Motor potenometer The setpoint is generated by the "Motor potenometer"
funcon.
4Mot
or potenometer se
tpoint source
^ 198
Conguring the network
General network sengs
103