EasyManua.ls Logo

Lenze i510 - Page 154

Lenze i510
250 pages
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
Parameter Name / value range / [default seng] Info
0x2838:001
(PAR 203/001)
Start/st
op conguraon: Start method
(Start/stop confg: Start method)
Seng can only be changed if controller inhibit is
acve.
Starng performance of the inverter.
0 Normal Aer switch-on, the standard ramps are acve.
Acceleraon me 1 can be set in 0x2917 (PAR 220).
Deceleraon me 1 can be set in 0x2918 (PAR 221).
1 Start with DC braking Aer switch-on, the "DC braking" funcon is acve for the me set in
0x2B84:002 (PAR 704/002).
4DC braking ^
153
2 Flying Start Aer switch-on, the "Restart on the y"
funcon is acve.
This funcon mak
es it possible t
o r
es
tart a coasng motor on the y dur-
ing operaon without speed feedback. Synchronicity between the inver-
ter and the motor is coordinated so that the transion to the rotang
drive is eected without jerk at the me of connecon.
4Flying restart funcon ^ 182
0x2838:003
(PAR 203/003)
St
art/stop conguraon: Stop method
(Start/stop confg: Stop method)
Behaviour aer the "Stop" command.
0 Coasng The motor coasts down to standsll.
1 Standard Ramp The motor is brought to a standsll with deceleraon me 1 (or deceler-
aon me 2, if acvated).
Deceleraon me 1 can be set in 0x2918 (PAR 221).
Deceleraon me 2 can be set in 0x291A (PAR 223).
4Frequency limits and ramp mes ^ 73
2 Quick stop ramp The motor is brought to a standsll with the deceleraon me set for
the "Quick s
t
op" funcon.
Deceleraon
me f
or quick stop can be set in 0x291C (P
AR 225).
Addional funcons
DC braking
154
Phone: 800.894.0412 - Fax: 888.723.4773 - Web: www.actechdrives.com - Email: info@actechdrives.com

Table of Contents

Other manuals for Lenze i510

Related product manuals