Parameter Name / value range / [default seng] Info
0x2838:001
(PAR 203/001)
Start/st
op conguraon: Start method
(Start/stop confg: Start method)
•
Seng can only be changed if controller inhibit is
acve.
Starng performance of the inverter.
0 Normal Aer switch-on, the standard ramps are acve.
•
Acceleraon me 1 can be set in 0x2917 (PAR 220).
•
Deceleraon me 1 can be set in 0x2918 (PAR 221).
1 Start with DC braking Aer switch-on, the "DC braking" funcon is acve for the me set in
0x2B84:002 (PAR 704/002).
4DC braking ^
153
2 Flying Start Aer switch-on, the "Restart on the y"
funcon is acve.
This funcon mak
es it possible t
o r
es
tart a coasng motor on the y dur-
ing operaon without speed feedback. Synchronicity between the inver-
ter and the motor is coordinated so that the transion to the rotang
drive is eected without jerk at the me of connecon.
4Flying restart funcon ^ 182
0x2838:003
(PAR 203/003)
St
art/stop conguraon: Stop method
(Start/stop confg: Stop method)
Behaviour aer the "Stop" command.
0 Coasng The motor coasts down to standsll.
1 Standard Ramp The motor is brought to a standsll with deceleraon me 1 (or deceler-
aon me 2, if acvated).
•
Deceleraon me 1 can be set in 0x2918 (PAR 221).
•
Deceleraon me 2 can be set in 0x291A (PAR 223).
4Frequency limits and ramp mes ^ 73
2 Quick stop ramp The motor is brought to a standsll with the deceleraon me set for
the "Quick s
t
op" funcon.
•
Deceleraon
me f
or quick stop can be set in 0x291C (P
AR 225).
Addional funcons
DC braking
154