0x4046
(PAR 755)
Acvaon of parameter se
t
(Param. set mode)
Selecon of the acvaon method for the parameter change-over.
0 Via command (only if the controller is
inhibited)
The parameter set selected via the "Parameter set selecon bit 0" and
"Parameter set selecon bit 1" funcons is acvated if the trigger
assigned in 0x2631:040 (PAR 400/040) of the "Load parameter set" func-
on supplies a FALSE-TRUE edge AND the inverter is inhibited.
1 Via command (immediately) The parameter set selected via the "Parameter set selecon bit 0" and
"Parameter se
t selecon bit 1" funcons is acvated if the trigger
assigned in 0x2631:040 (PAR 400/040) of the "Load parameter set" func-
on supplies a FALSE-TRUE edge.
2 If the selecon is changed (only if the
controller is inhibited)
The par
ameter set selected via the "Parameter set selecon bit 0" and
"Parameter set selecon bit 1" funcons is acvated if a state change of
these selecon bits takes place AND the inverter is inhibited.
3 If the selecon is changed (immediately) The parameter set selected via the "Parameter set selecon bit 0" and
"Parameter set selecon bit 1" funcons is acvated if a state change of
these selecon bits takes place.
0x4047:001
(PAR 756/001)
Parameter change-over error message: Status
(Param. set status: Param. set error)
Read only
Error message for the "Parameter set changeover" funcon.
In the event of an error
, an error status is shown here, and in
0x4047:002 (PAR 756/002) the number of the list entry in which the
error has occurred is displayed (in connecon with the value set
selected).
If several err
ors occur at the same me, only the rst incorrect list
entry will be displayed. Hence, aer eliminaon of the displayed error
and repeated acvaon, more errors may be displayed.
The parameter list will always be processed from beginning to end,
even if errors occur in the meanme.
0 No fault
33803 Invalid data type
33804 Range violaon
33806 Invalid index
33813 No element selected
33815 Wring impermissible
33816 Device not inhibited
33829 Invalid subindex
33837 Access impermissible
33865 No subindexes
0x4047:002
(PAR 756/002)
Paramet
er change-over error message: List entry
(Param. set status: ParSet error loc)
Read only
Error message for the "Parameter set changeover" funcon.
In the event of an error
, the number of the list entry for which the
error displayed in 0x4047:001 (PAR 756/001) has occurred is shown
here.
0x2631:040
(PAR 400/040)
Funcon assignment: Load paramet
er set
(Funcon list: Load param.set)
Seng can only be changed if controller inhibit is
acve.
For possible sengs see descripon for
0x2631:001 (PAR 400/001). ^ 188
Assignment of a trigger for the "Load parameter set" funcon.
Trigger = FALSE-TRUE edge: parameter change-over to the value set
selected via "Parameter set selecon bit 0" and "Parameter set selecon
bit 1".
Trigger = FALSE: no acon.
Notes:
The acvaon method for the "Parameter change-over" funcon can
be selected in 0x4046 (PAR 755).
00 Not connected No trigger assigned (trigger is constantly FALSE).
0x2631:041
(PAR 400/041)
Funcon assignment: Parameter set selecon bit 0
(Funcon list: Par.set selecon b0)
Seng can only be changed if controller inhibit is
acve.
For possible sengs see descripon for
0x2631:001 (PAR 400/001). ^ 188
Assignment of a trigger for the "Parameter set selecon bit 0" funcon.
Selecon bit with the valency 2
0
for "Parameter change-over" funcon.
Trigger = FALSE: selecon bit = "0".
Trigger = TRUE: selecon bit = "1".
00 Not connected No trigger assigned (trigger is constantly FALSE).
0x2631:042
(PAR 400/042)
Funcon assignment: Parameter set selecon bit 1
(Funcon list: Par.set selecon b1)
Seng can only be changed if controller inhibit is
acve.
For possible sengs see descripon for
0x2631:001 (PAR 400/001). ^ 188
Assignment of a trigger for the "Parameter set selecon bit 1" funcon.
Selecon bit with the valency 2
1
for "Parameter change-over" funcon.
Trigger = FALSE: selecon bit = "0".
Trigger = TRUE: selecon bit = "1".
00 Not connected No trigger assigned (trigger is constantly FALSE).
Addional funcons
Paramet
er change-over
176