Parameter Name / value range / [default seng] Info
0x2631:010
(PAR 400/010)
Funcon assignment: Fow
ard jog (CW)
(Funcon list: Forward jog)
•
Seng can only be changed if controller inhibit is
acve.
•
For possible sengs see descripon for
0x2631:001 (PAR 400/001). ^ 188
Assignment of a trigger for the "Foward jog (CW)" funcon.
Trigger = TRUE: drive traverses in forward rotang direcon (CW) with
the preset value 5.
Trigger = TRUE-FALSE edge: drive is stopped again.
Notes:
•
The preset value 5 can be set in 0x2911:005 (PAR 450/005).
•
The stop method can be selected in 0x2838:003 (PAR 203/003).
•
Jog operaon has a higher priority than a stop command. If jog opera-
on is acve, a stop command that has been triggered has no eect!
•
However
, jog operaon can be interrupted by the "Quick stop" func-
on.
•
Jog operaon cannot be started automacally. The "Start at s
witch-
on" opon in 0x2838:002 (PAR 203/002) does not apply to jog opera-
on.
•
If "Foward jog (CW)
" and "Backward jog (CCW)" are acvated at the
same me, the drive is stopped using the s
top method and jog opera-
on must be triggered again.
00 Not connected No trigger assigned (trigger is constantly FALSE).
0x2631:011
(PAR 400/011)
Funcon assignment: Backward jog (CCW)
(Funcon list: Backward jog)
•
Seng can only be changed if controller inhibit is
acve.
•
For possible sengs see descripon for
0x2631:001 (PAR 400/001). ^ 188
Assignment of a trigger for the "Backward jog (CCW)" funcon.
Trigger = TRUE: drive traverses in backward rotang direcon (CCW)
with the preset value 6.
Trigger = TRUE-FALSE edge: drive is stopped again.
Notes:
•
The preset value 6 can be set in 0x2911:006 (PAR 450/006).
•
The stop method can be selected in 0x2838:003 (PAR 203/003).
•
Jog operaon has a higher priority than a stop command. If jog opera-
on is acve, a stop command that has been triggered has no eect!
•
However
, jog operaon can be interrupted by the "Quick stop" func-
on.
•
Jog operaon cannot be started automacally. The "Start at s
witch-
on" opon in 0x2838:002 (PAR 203/002) does not apply to jog opera-
on.
•
If "Foward jog (CW)
" and "Backward jog (CCW)" are acvated at the
same me, the drive is stopped using the stop method and jog opera-
on must be triggered again.
00 Not connected No trigger assigned (trigger is constantly FALSE).
0x2631:013
(PAR 400/013)
Funcon assignment: Rev
ersal
(Funcon list: Reversal of rot. dir.)
•
Seng can only be changed if controller inhibit is
acve.
•
For possible sengs see descripon for
0x2631:001 (PAR 400/001). ^ 188
Assignment of a trigger for the "Reversal" funcon.
Trigger = TRUE: the setpoint specied is inverted (i. e. the sign is inver-
ted).
Trigger = FALSE: no acon / deacvate funcon again.
13 Digital input 3 State of X3/DI3, taking an inversion set in 0x2632:003 (PAR 411/003) into
consideraon.
Flexible I/O conguraon
Controller enable, starng & stopping, reversal
192