Parameter Name / value range / [default seng] Info
0x29C0:002 Field controller sengs: Reset me
1.0 ... [45.5]* ... 6000.0 ms
•
Default seng depending on the size.
R
eset me Tn of the eld controller.
0x29E0:001 Field weakening controller sengs: Gain
0.000 ... [0.000]* ... 2000000.000 Vs/V
•
Default seng depending on the size.
Gain factor Vp of the eld weakening controller.
0x29E0:002 Field weakening controller sengs: Reset me
1.0 ... [1478.3]* ... 240000.0 ms
•
Default seng depending on the size.
R
eset me Tn of the eld weakening controller.
0x2B40:001 SLVC: Gain
0.0000 ... [0.2686]* ... 1000.0000 Hz/A
•
Default seng depending on the size.
Gain of the SL
VC-Q controller.
0x2B40:002 SLVC: Reset me
1.0 ... [2.3]* ... 2000.0 ms
•
Default seng depending on the size.
Reset me of the SLVC-Q controller.
0x2900:001
(PAR 332/001)
Speed controller parameters: Gain
(Speed controller: Speed contr.: gain)
0.00000 ... [0.00193]* ... 20000.00000 Nm/rpm
•
Default seng depending on the size.
Gain factor Vp of the speed controller.
0x2900:002
(PAR 332/002)
Speed controller parameters: Reset me
(Speed controller: Speed contr.: me)
1.0 ... [80.0]* ... 6000.0 ms
•
Default seng depending on the size.
Reset me Ti of the speed controller.
0x2915
(PAR 210)
Minimum frequency
(Min. frequency)
0.0 ... [0.0] ... 599.0
Hz
Lower limit value for all frequency setpoints.
0x2916
(PAR 211)
Maximum frequency
(Max. frequency)
0.0 ... [50.0] ... 599.0 Hz
Upper limit value for all frequency setpoints.
0x2942:001
(PAR 334/001)
Current controller parameters: Gain
(Current controller: I-contr.: gain)
0.00 ... [42.55]* ... 750.00 V/A
•
Default seng depending on the size.
Gain factor Vp of the current controller.
0x2942:002
(PAR 334/002)
Current controller parameters: Reset me
(Current controller: I-contr.: me)
0.01 ... [4.50]* ... 2000.00 ms
•
Default seng depending on the size.
Reset me Ti of the current controller.
0x2BA1:003
(PAR 718/003)
Flying restart circuit: Restart me
(Flying restart circuit: Flying restart me)
1 ... [5911]* ... 60000 ms
•
Default seng depending on the size.
Restart me for ying restart process.
•
The duraon of the ying restart process can be inuenced by the set-
ting of the restart me.
•
A reducon of the restart me causes an accelerated ying restart
process and therefore a reduced ying restart duraon.
0x6073
(PAR 324)
Max current
(Max current)
0.0 ... [200.0] ... 3000.0 %
Maximum overload current of the inverter.
•
100 % ≡ rated motor current 0x6075 (PAR 323)
•
If the current consumpon of the motor exceeds this current limit,
the inverter changes its dynamic behaviour, in order to counteract
this exceedance.
•
If the change in the dynamic behaviour carried out by the inverter
does not result in exing the overcurrent state, the inverter outputs
an error.
Note!
This parameter is not idencal to the so-called ulmate motor current
I
ULT
!
•
The ulmate motor current set in 0x2D46:001 (PAR 353/001) is a limit
value for synchronous motors that serves to protect their magnets.
•
The value to be set here should always be considerably below the ul-
mate motor current!
Motor control
Motor control selecon
Sensorless v
ector control (SLVC)
83