8 Operation
Maschinenfabrik Reinhausen GmbH 2020 1033587317/21 EN TAPCON
®
Device ID
You can use this parameter to assign a device ID to the device in order that
it can be identified in the IEC 61850 network.
Access point
You can use this parameter to assign a name to the access point in the IEC
61850 network.
Edition
You can use this parameter to switch between edition 1 and edition 2 of the
IEC 61850 control system protocol.
8.8.1.1 Downloading an ICD file
You can download the ICD file from the device via the Import/Export Man-
ager [Section 8.28, Page 251]. To do this, you have to establish an Ether-
net connection between the device and your PC.
8.8.1.2 Importing CID/SCD file (optional)
Note the following definitions for importing a CID file or SCD file.
Only the following elements may differ between the imported IED and the
exported IED from the TEMPLATE.icd.
DataSet elements can be created in each LN
ReportControl elements can be created in the LN containing the associ-
ated DataSet
IP address (if this is not present, the preset one is used)
Subnet mask (if this is not present, the preset one is used)
Gateway IP address (if this is not present, the preset one is used)
Name of IED (IED name)
Name of AccessPoint (AccessPoint attribute name)
Name of logical device (LDevice attribute inst)
OSI-PSEL, OSI-SSEL, and OSI-TSEL cannot be adjusted.
The SCD file may contain no more than 45 IEDs. It may take several min-
utes to import a complete SCD file. The SCD file should only contain the
IEDs needed.
You can import the CID/SCD file via the Import/Export Manager. To do so,
proceed as follows:
1. Go to Settings > Import.
2. Select and import the desired CID/SCD file.