8 Operation
Maschinenfabrik Reinhausen GmbH 2020188 3587317/21 ENTAPCON
®
8.18.2 Configuring parallel operation
In the Parallel operation menu item, you can set the parameters needed for
parallel transformer operation.
Activating parallel operation On
Parallel operation method Master
Circulating reactive current sens... 0.0%
Circulating reactive current bloc... 20.0%
Desired load stress type Inductive
Master/follower current blocking Off
Master/follower switching charact... Sequential
Error if no communication present No error
Behavior if no communication pres... Independent regulation
Parallel operation error delay ti... 10s
Figure129: Parallel operation
1. Go to Settings > Parameters > Grid > Parallel operation.
2. Select the desired parameter.
3. Set the desired parameter.
4. Press the Accept button to save the modified parameter.
Activating parallel operation
You can use this parameter to activate parallel operation.
Parallel operation method
You can use this parameter to set the parallel operation method. You can
select the following options:
Option Description
Master The device is designated as
the master.
Tap synchronization [►Sec-
tion 8.18.1.1, Page 180] par-
allel operation method
Follower The device is designated as
the follower.
Auto. tap synchroniza-
tion
Automatic assignment of
master or follower.
If a master is not detected,
the device with the lowest
CAN bus address is auto-
matically designated as the
master. All other devices are
designated as followers.