8 Operation
Maschinenfabrik Reinhausen GmbH 2020 973587317/21 EN TAPCON
®
8.5 Setting the device time
You can set the the device time manually or automatically via an SNTP time
server. The device must be connected to a time server via Ethernet for this
purpose. You can operate SNTP and PTP at the same time. In this case, the
PTP time is queried in slave operation.
Time synchronization via SNTP Off
Time synchronization via SNTP Off
Synchronization interval 60s
PTP version IEEE 1588-2008
Automatic Daylight Savings Time Off
Time zone (UTC+01:00) Amsterdam, Berlin,
Activate second time server Off
SNTP time server 2 0.0.0.0
Figure78: Time synchronization
1. Go to Settings > Parameters > System > Time synchronization.
2. Select the desired parameter.
3. Set the parameter.
4. Press the Accept button to save the modified parameter.
Time synchronization via SNTP
You can use this parameter to activate time synchronization using an SNTP
time server.
SNTP time server
You can use this parameter to enter the IP address of a SNTP time server. If
you are using a time server, the device uses the time of the time server as
the system time.
Be sure to enter a valid time server address that is not 0.0.0.0, otherwise it
will not be possible to connect to the device.
Synchronization interval
You can use this parameter to set the interval at which the device is to call
up the time from the time server.