8 Operation
Maschinenfabrik Reinhausen GmbH 2020 1953587317/21 EN TAPCON
®
8.18.5 Detecting parallel operation via topology
The topology function is used to detect which transformers are in parallel op-
eration based on the position of the circuit breakers. Each circuit breaker is
fitted with an auxiliary contact so that its status can be reported for this pur-
pose.
8.18.5.1 Topology with fixed master/client
A device (topology master) records the status of the circuit breakers via digi-
tal inputs and reports which devices are taking part in parallel operation to
the connected devices (topology clients) over the CAN bus.
Topology master
Topology client
Topology client
Figure134: Operating principle for master with voltage regulation
You have to set the following parameters for the topology with fixed master/
client function.
Parameters Topology master Topology client
Prim/sec. topology Primary/Secondary -
CAN address 1(2)...16 de-
vice name
User-defined -
CAN bus address 1 2...16
Circuit breaker configura-
tion
User-defined -
Table68: Configuring the topology