11 Event messages
Maschinenfabrik Reinhausen GmbH 2020280 3587317/21 ENTAPCON
®
11 Event messages
No. Name Description Remedy
1 Limit value U< Value has fallen below the limit value for
undervoltage U<.
Check the current operating conditions of
the transformer and the set U< parame-
ters.
2 Limit value U<< Value has fallen below the limit value for
undervoltage U<<.
Check the current operating conditions of
the transformer and the set U<< parame-
ters.
3 Limit value U> The limit value for overvoltage U> has
been exceeded.
Check the current operating conditions of
the transformer and the set U> parame-
ters.
4 Limit value U>> The limit value for overvoltage U>> has
been exceeded.
Check the current operating conditions of
the transformer and the set U>> parame-
ters.
5 Limit value I< Value has fallen below the limit value for
undercurrent I<.
Check the current operating conditions of
the transformer and the set I< parame-
ters.
6 Limit value I<< Value has fallen below the limit value for
undercurrent I<<.
Check the current operating conditions of
the transformer and the set I<< parame-
ters.
7 Limit value I> The limit value for overcurrent I> has
been exceeded.
Check the current operating conditions of
the transformer and the set I> parame-
ters.
8 Limit value I>> The limit value for overcurrent I>> has
been exceeded.
Check the current operating conditions of
the transformer and the set I>> parame-
ters.
9 Limit value S< Value has fallen below the limit value for
apparent power S<.
Check the current operating conditions of
the transformer and the set S< parame-
ters.
10 Limit value S<< Value has fallen below the limit value for
apparent power S<<.
Check the current operating conditions of
the transformer and the set S<< parame-
ters.
11 Limit value S> The limit value for apparent power S>
has been exceeded.
Check the current operating conditions of
the transformer and the set S> parame-
ters.
12 Limit value S>> The limit value for apparent power S>>
has been exceeded.
Check the current operating conditions of
the transformer and the set S>> parame-
ters.
13 Limit value P< Value has fallen below the limit value for
active power P<.
Check the current operating conditions of
the transformer and the set P< parame-
ters.
14 Limit value P<< Value has fallen below the limit value for
active power P<<.
Check the current operating conditions of
the transformer and the set P<< parame-
ters.
15 Limit value P> The limit value for active power P> has
been exceeded.
Check the current operating conditions of
the transformer and the set P> parame-
ters.