EasyManua.ls Logo

MR TAPCON - Function Tests

MR TAPCON
334 pages
Print Icon
To Next Page IconTo Next Page
To Next Page IconTo Next Page
To Previous Page IconTo Previous Page
To Previous Page IconTo Previous Page
Loading...
7 Commissioning
Maschinenfabrik Reinhausen GmbH 202080 3587317/21 ENTAPCON
®
2. Go to Settings > Commissioning wizard.
Figure68: Calling up the commissioning wizard
3. Press the Next button to launch the commissioning wizard.
4. Follow the on-screen instructions.
Once you have entered all of the parameters relevant to commissioning,
continue with the function test [Section 7.5, Page 80].
7.5 Function tests
Before switching from manual mode to auto mode, Maschinenfabrik Rein-
hausen recommends carrying out function tests. These function tests are de-
scribed in the following sections. Note the following points for all function
tests:
You must ensure that REMOTE mode is disabled before you can control
the on-load tap-changer manually in manual mode.
You can only activate the on-load tap-changer manually in manual mode
using the and keys.
You have to be logged in to the device as a user with a parameter config-
urator or administrator user role.
When in delivery status, you can log in as the administrator as follows:
User name: admin
Password: admin
During the function test, you must set the most important parameters. Details
on the parameters listed can be found in the Operation [Section 8, Page
87] chapter.

Table of Contents

Related product manuals