8 Operation
Maschinenfabrik Reinhausen GmbH 2020242 3587317/21 ENTAPCON
®
Function Data display Diagnostics Operator Parameter
configurator
Administrator
Set date and time - - + + +
Calling up the commissioning
wizard
- - - + +
Calibrate resistor contact se-
ries
- - - + +
Actuation of the RAISE,
LOWER, REMOTE, AVR
AUTO, and AVR MANUAL
keys
- - + + +
Setting topology - - - + +
Configuring analog inputs and
outputs
- - - + +
Configuring digital inputs and
outputs
- - - + +
Setting TPLE - - - + +
Configuring data points - - - + +
Calling up the maintenance
wizard
- - - + +
Changing tap position table - - - + +
Enabling ECOTAP Modbus - - - + +
Adding sensors to the MR
sensor bus
- - - + +
Table87: Access rights permanently linked to the roles
8.26.2 Changing the password
All users can change their passwords provided that the user account is not
set up as a group account. You can only change a group account's pass-
word if you are logged in as the administrator.
Note that the password must satisfy the following requirements:
▪ At least eight characters
▪ At least three of the four following character types
– Upper case letters
– Lower case letters
– Numbers
– Special characters